Motor Circuit Breaker, Tesys Gv5, 3P, 150A, Icu 36Ka, Thermal Magnetic GV5P150F APC

Clique no botão ao lado para assistir ao vídeo relacionado ao produto.

Assistir Vídeo

Motor Circuit Breaker, Tesys Gv5, 3P, 150A, Icu 36Ka, Thermal Magnetic GV5P150F APC

Código: GV5P150F Marca:

Para mais informações entre em contato conosco através do telefone (11) 5091-2400 ou através do Fale Conosco

Incluir no Orçamento Estoque: Disponível
TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V. It provides thermal magnetic protection and additional protections, breaking capacity Icu 36kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors). Thermal protection adjustable by dials with a setting current Ir in range 70-150A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In. Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Para mais informações entre em contato conosco através do telefone (11) 5091-2400 ou através do Fale Conosco

Incluir no Orçamento Estoque: Disponível
Selos